1. MODEL AND RATINGS
Product SeriesWD400Duty RatingG - Heavy Duty
ModelWD400-S2-2R2G-BFrame SizeFrame Size 2
Input SupplySingle-phase, 200–240 VAC ±10%Supply Frequency50 / 60 Hz ±5%
Rated Motor Power2.20 kWHorsepower3 HP
Rated Input Line Current20 AMax. Continuous Output Current10 A
Max. Instantaneous Current15 AOverload Capacity150% of rated current for 60 s




2. MOTOR CONTROL PERFORMANCE
Supported Motor TypesInduction motor (IM); permanent magnet synchronous motor (PMSM)Control ModesV/F, sensorless vector control (SVC), field-oriented vector control (FVC)
Starting Torque200%Torque Step Response≤2 ms
IM SVC Speed Range1:500PMSM SVC Speed Range1:200
FVC Speed Stability Accuracy0.02%FVC Speed Fluctuation0.05%
FVC Torque Control Accuracy±2%SVC Torque Control Accuracy±3% above 5 Hz
Flux-Weakening CapabilityUp to 5×Safety FunctionSafe Torque Off (STO)




3. I/O, COMMUNICATION AND EXPANSION
Analog Inputs2 channels: 0–10 V / 0–20 mA / 4–20 mAAnalog Outputs1 channel: 0–10 V / 0–20 mA / 4–20 mA
Digital Inputs5 programmable inputs; max. input frequency 1 kHzDigital Outputs1 open-collector output + 1 high-speed pulse output
Relay Outputs1 programmable relay outputStandard CommunicationRS485, Modbus RTU
Expansion Slots2 slots: SLOT and SLOT2Optional FieldbusPROFINET, PROFIBUS-DP, EtherNET, CANopen
Speed Feedback OptionsABZ incremental encoder; resolverI/O ExpansionDI, DO, AO, relay and temperature input expansion




4. MECHANICAL AND ENVIRONMENTAL DATA
Overall Dimensions (W1 × D1 × H1)100 × 155 × 242 mmMounting Dimensions (W2 × H2)84 × 232 mm
Mounting Holes4 × Ø5Packing Dimensions (L × W × H)29 × 22 × 17 cm
Gross Weight2.2 kgDegree of ProtectionIP20
Cooling MethodForced-air coolingInstallationWall-mounted or floor-standing, subject to cabinet arrangement
Operating Temperature−10 to +50 °C; derate by 1.5% per °C above 40 °CStorage Temperature−20 to +60 °C
DC ReactorNot built inBraking UnitBuilt in as standard




5. FUNCTIONS, PROTECTION AND COMPLIANCE
Key Control FunctionsEnergy-saving control, speed tracking, droop control, master-slave control, DC braking, overexcitation rapid deceleration, automatic voltage regulation (AVR), torque boost and slip compensation
Protection FunctionsOvercurrent, overvoltage, undervoltage, drive overload, motor overload, input/output phase loss, overheating, ground short circuit, braking resistor fault, encoder fault and back-EMF fault
StandardsIEC 61800-5-1; GB 12668; EMC performance in accordance with IEC 61800-3
WOLONG  |  www.vfdpower.com


Contact Us

Be the first to know about our new product launches, latest blog posts and more.
Founded in 1984, Wolong is a global leader in motor and drive technology, providing safe, efficient,...

Any question or request?

Click below, we’ll be happy to assist. Contact Us
Copyright © 2026 Wolong VFD Electric Group. All rights reserved.