Choosing a VFD starts with the load, not the catalogue: identify whether your application is variable-torque (pumps, fans), constant-torque (conveyors, mixers) or constant-power (spindles, mills), then match the motor ratings, pick a control mode and confirm the protection class. A 7.5 kW pump drive and a 7.5 kW conveyor drive are usually different selections even though the power rating is the same. This guide walks through the five selection steps with a load-type table.

| Load type | Typical equipment | Torque behaviour | Selection focus |
| Variable torque | Centrifugal pumps, fans, blowers | Torque ∝ speed²; power ∝ speed³ | Light duty class, energy saving, soft start |
| Constant torque | Conveyors, mixers, extruders, compressors | Torque roughly constant over speed range | Heavy duty class, torque at low speed, current margin |
| Constant power | Machine spindles, mills, winders | Power constant; torque falls as speed rises | Field-weakening range, speed range rating |
| High inertia | Centrifuges, large flywheels, crushers | Long acceleration, possible regenerative braking | Oversize margin, braking resistor or unit |
The drive must match the motor's rated voltage, full-load current and frame characteristics. Key checks: the rated current of the drive at the operating voltage must cover the motor's full-load current (plus a sensible margin, typically 10–20% for constant-torque duty); single-phase input limits output power; and the maximum motor cable length needs output reactors on long runs. For the full current-based method see our VFD sizing guide.
Match the control mode to what the process needs – a fan rarely needs closed-loop accuracy, while a hoist absolutely does.
Check the installation environment before finalising the model: enclosure IP rating for dust and moisture; ambient temperature derating (most drives derate above 40 °C, and many are limited to 50 °C); altitude derating above 1000 m (typically 1% per 100 m above); and input voltage quality including harmonic limits – see our energy efficiency article for why harmonics matter to the whole installation.
Can one VFD model cover both pumps and conveyors? Many drives have light- and heavy-duty ratings in one frame, so one model family covers both – but the continuous and overload ratings you select differ. Specify the duty class at order time.
How important is the control mode for a pump? V/f is usually sufficient for pumps and fans; vector control helps when you need torque at low speed or better speed holding. Our VFD FAQs cover control questions in more detail.
Not sure which drive matches your motor and load? Our selection team can work from your motor nameplate and process data. Start with our VFD selection guide, and see the high-voltage VFD page for larger ratings.