An overcurrent (OC) trip means the drive's output current exceeded its protection threshold, and the most common causes are an acceleration ramp too short for the load, wrong motor parameters, a damaged motor or cable, or a mechanically jammed machine. The fastest fix path: check the trip timing, run motor autotuning, lengthen the acceleration time, and inspect the motor and cable insulation. This article explains how OC protection works, the causes, and a step-by-step diagnosis with prevention settings.

The drive continuously compares its output current with the limit set by the overload class and the current-limitation parameter. A trip fires in two cases: an instantaneous overcurrent (usually a hardware fault, e.g. a short circuit or a faulty IGBT) or an overcurrent over time (usually a control issue – the motor draws more than the drive can deliver). IEC 61800-5-1 requires the drive to protect itself and the motor within defined limits, which is why OC trips are designed to be fast and safe rather than to indicate damage.
| Step | Action | What it tells you |
| 1 | Record when the trip occurs: during start, acceleration, or steady run | Start/acceleration → ramp or parameters; steady run → load or insulation |
| 2 | Run motor autotuning with the motor uncoupled if possible | Corrects motor model; fixes most parameter-related trips |
| 3 | Lengthen the acceleration ramp and re-test | Confirms or excludes acceleration as the cause |
| 4 | Measure motor phase current and insulation (megger) on the motor and cable | Detects winding or insulation damage |
| 5 | Check the machine mechanically (bearings, coupling, blockage) | Detects jam or increased friction |
Does an OC trip damage the VFD? The protection is designed to protect the drive; one trip rarely causes damage. Repeated trips under load stress the power stage, so find and fix the cause rather than simply resetting. See our overvoltage troubleshooting guide for the related DC-bus fault.
My drive trips at the same speed every time – why? A repeatable trip point usually points to a mechanical resonance or a V/f curve mismatch at that speed, or a winding fault that appears at that load point. Measure the current at that speed and compare with the drive rating – our sizing guide explains the ratings.
If OC trips persist after these checks, contact our service team with the fault code and trip log – see our VFD FAQs and the low-voltage VFD range.